|
Lighting Retrofit Report
We have completed a six year $6 million lighting retrofit program,
resulting in a decrease of around $1 million per year in lighting
energy cost. This project, and some of our measurements of electronic
ballast reliability and optical reflector performance, are described
in the following three documents:
Managing a Large Lighting Retrofit Project
Field Experience with High-Frequency Ballasts
Performance of Retrofit Optical Reflectors
If you have questions about Energy Conservation Projects at the
University of California at Berkeley, please contact:
Raul Abesamis, Energy Engineer
(510) 642-6254
Fax: 510-643-6588
abesamis@berkeley.edu
The Berkeley Campus of the University of California have over 100
buildings of varying age and function, comprising nearly 9 million
square feet. The campus electrical bill has been continually climbing
and is approximately one million dollars per month. In 1986 funding
was obtained from a State of California bond issue to embark upon
a six-year program to improve the energy efficiency of the lighting
in around 60 state-supported buildings. We completed the six million
dollar project using a novel project management system, which has
resulted in the successful installation of over 87,000 high-frequency
ballasts, 16,000 optical reflectors in delamped luminaries, and
many other energy-saving devices. This has resulted in a 25%-40%
decrease in lighting energy use. In order to maximize lighting energy
efficiency, survey results must be used to individually analyze
spaces and specify retrofits tailored to the requirements of the
different spaces.
Managing a Large Lighting Retrofit Project
Jeffrey D. Kessel, P.E.
Physical Plant-Campus Services
University of California
Berkeley, CA 94720
ABSTRACT
The Berkeley Campus of the University of California has over 100
buildings of varying age and function, comprising nearly 9 million
square feet. The campus electrical bill has been continually climbing
and is approximately one million dollars/month. In 1986 funding
was obtained from a State of California bond issue to embark upon
a six year program to improve the energy efficiency of the lighting
in around 60 state-supported buildings. We completed the six million
dollar project using a novel project management system, which has
resulted in the successful installation of over 87,000 high-frequency
ballasts, 16,000 optical reflectors in delamped luminaires, and
many other energy-saving devices. This has resulted in a 25%-40%
decrease in lighting energy use. In order to maximize lighting energy
efficiency, survey results must be used to individually analyze
spaces and specify retrofits tailored to the requirements of the
different spaces. This paper describes our approach and methods.
PRELIMINARY ANALYSIS OF LIGHTING RETROFIT OPPORTUNITIES
Before applying for financing we had to convince ourselves that
retrofit hardware was available with cost, performance, and reliability
that would ensure a cost-effective installation to reduce energy
use. We began by collecting data on candidate systems and brands.
Whenever possible we relied on data from independent test labs and
on information from experienced users of the products. Price quotes
were based on realistic quantities. For example, our ballast orders
usually exceeded 2,000 units. When we obtained quotes from lighting
maintenance contractors who would be changing out the old ballasts
we made clear that the unit prices quoted should reflect a future
contract that would represent at least six months work.
There are many lighting retrofits that can be used to increase
efficiency, and no way to know what mix of retrofits will be used
until a detailed analysis of each space is conducted. We were sure,
however, that high-frequency ballasts would be used throughout our
project. Furthermore, we wanted to install reflectors with delamping
in order to reduce lighting levels in overlit spaces. The following
two cases show the assumptions we used in our preliminary analysis
of these two common retrofits.
Ballast Swap
When we determined, using methods discussed below in the section
titled Analysis of the Spaces, that a space was not overlit, then
the luminaires were specified to be cleaned and relamped, and the
old ballasts removed and replaced with high-frequency ballasts.
The charge for labor and lamps came to $13.00 for a 2F40 luminaire,
and the cost of the ballast, which was supplied to the lighting
maintenance contractor by the University, was $22.00. Thus
for $35.00 the old fixture is renovated. We used 34 watt T-12 (3500
K) lamps on campus, and we assumed that the old ballast was a standard
magnetic ballast operating at 79 w., and that the new ballast operates
at 61 w. The ballast swap reduces power by 18 w = 0.018 kw per luminaire.
In a space lighted for 3,000 hours per year, at a cost of electricity
of $0.08, the simple payback for one ballast swap was calculated
to be: SP = [cost] / [annual savings]
= [35.00] / [(.018w)*(3000hrs/yr)*(0.08 $/kwh)]
= 8.1 years. Today's paybacks should be shorter due to lower ballast
prices for the T-8 system ballast.
If the luminaire is used 8760 hours per year, at an average cost
of electricity of $0.06/kwh, then the SP = 3.7 years.
The difference in rate between $0.08 and $0.06 reflects higher
utility charges during periods of peak use.
In cases where spaces are overlit, it may be possible to install
partial power ballasts with reduced light output, or to convert
from HO to slimline by changing lamp sockets. Table 1 presents the
power level for various lamp/ballast systems. The values in parentheses
are the system power when energy-saver lamps are used.
TABLE 1. BALLAST SYSTEM POWER, WATTS
| Ballast / System |
Older Magnetic |
Efficient Magnetic |
High Frequency |
| 2FO32, octron |
84 (NA) |
77 (NA) |
65 (NA) |
| 2F40, rapid start |
96 (79) |
87 (72) |
73 (61) |
| 2F96, slimline |
180 (150) |
163 (137) |
144 (120) |
| 2F96HO, high output |
264 (225) |
240 (204) |
211 (180) |
Although our campus experienced poor reliability when using first-generation
high frequency ballasts in the late 1970s, our present experience
with ballast reliability is very satisfactory. Moreover, failures
within the three year year warranty period qualify for free replacements
as well as a $10 labor rebate.
Reliability results after three years of operation are reported
in [Abesamis, 1990]. We have updated our measurement of reliability
after the installation of over 87,000 high frequency ballasts (80%
T-12 rapid start, 17% slimline, and 3% HO) between December, 1986
and December, 1992. We have recorded 3,900 failed ballasts out of
423,700 ballast-years experience, resulting in an average annual
failure rate of 0.9 %, for the ballasts made by the two manufacturers
supplying most of the project's ballasts.
Optical Reflectors and Delamping
Some optical reflector vendors claim that their installation will
increase light levels, even while removing half the lamps. In order
to evaluate reflector performance we conducted a "Reflectoff"
that compared the illuminance from a basecase luminaire (cleaned
and fully lamped with new stable lamps) to the illuminance from
the same fixture using one-half the quantity of the same lamps and
an optical reflector. The results are presented in [Kessel, 1990]
and are summarized in Table 2.
TABLE 2. OPTICAL REFLECTOR PERFORMANCE
| System |
Illuminance, footcandles |
Power, watts |
| Anodized Aluminum |
61.5 |
61 |
| Anodized Aluminum with Dielectric Coating |
71 |
61 |
| Silver Laminate |
71 |
61 |
| Basecase (4 lamps) |
100 |
151 |
We also measured the distance out from the main axis of the luminaire
at which the illuminance dropped to 1/2 its value directly under
the luminaire. This "half-max" distance decreased by around
15% for all the reflectors we measured. Although this decrease in
uniformity is not significant for most applications, it should be
taken into account when tasks are located midway between luminaires.
Note that this decrease in high-angle luminance may advantageously
decrease glare in some situations.
Spaces that are overlit such that they can tolerate a reduction
in illuminance of at least 29% may do well with removal of half
the lamps and installation of an optical reflector above the lamps.
This mirror-like (specular) piece of sheet metal is designed to
increase the efficiency of the luminaire. Modifying a four lamp
luminaire produces nearly three lamps worth of light for the energy
cost of operating two lamps. Our cost in 1986 of $70.00 included
removal of old lamps and ballasts, provision and installation of
the reflector and two lamps, and installation of a University-supplied
ballast. The decrease in wattage in changing from two standard magnetic
ballasts to one high-frequency ballast is 2*79 - 61 = 97 w. Then
the simple payback for a luminaire operating 3000 hours per year
at $0.08/kwh is calculated to be: SP = [70.00] / [(97)*(3000)*(0.001)*(0.08)]
= 3.0 years. And for 8000 hrs/yr at $0.06/kwh, the SP = 1.4 years.
We made calculations such as these before beginning the project,
and realized that no matter what the final mix of retrofits eventually
specified, the overall project SP would likely be around five years.
Obviously this parameter is dependent on many factors, including
the cost of electricity, annual hours of use, type of existing equipment
and illuminance levels, utility rebates, and the cost of materials
and labor.
SURVEY OF THE FACILITY
We developed a form to record survey data for every space in a
building. The data included the room geometry and luminaire type
which are both required for subsequent cavity ratio method calculation
of available illuminance, which is then compared to the illuminance
required for the task in the space. The form also holds information
on occupancy patterns that indicate potential for motion sensor
lighting control. The surveyors also input data on the quantities
of luminaires in the daylighting zone (approximately within 15 feet
of windows) for possible application of photocell-controlled dimming
ballasts.
Ten engineering students were hired and trained to use the survey
form. Five million square feet of occupied space in sixty campus
buildings was surveyed in a period of approximately three months.
A building's data base comprised one data form for each room that
used electric lighting beyond a minimum number of kwh/yr, and a
plan sketch of the room showing workplaces, luminaires, switches,
and obstructions. In addition the surveyor developed a luminaire
glossary containing sketches of the different lighting fixtures
in the building.
The forms for each building were entered into a computer as a data
base file. One could use an ultra-sonic "tapeless" tape
measure, and a "palm-top" computer containing the survey
form as a spread sheet that could be subsequently down-loaded into
a data base running on a desk-top computer. Once a building's data
base was completed, analysis of the lighting began.
ANALYSIS OF THE SPACES
As an example, Figure 1 shows how a
building is divided into three families of identical spaces. The
input consists of room dimensions, reflectance, use (task), lamp
type, maintenance factor, and IES code number characterizing the
luminaires. The software then uses the cavity ratio method to calculate
maintained illuminance, and compares this to the stored value recommended
by the IES for the indicated task in the space. The result for each
family of spaces is a calculated quantity called the fullratio,
described below.
We attempted to prescribe a lighting retrofit that was suited to
each space in a building. Rather than use a single type of retrofit
throughout a building, we tailored each retrofit to the room in
which it would be installed. The key to this is to calculate or
measure the illuminance in each space and to compare this level
to the illuminance recommended for the on-going visual task by the
Illuminating Engineering Society of North America (IES). The IES
recommendations are for maintained illuminance levels, but the cavity-ratio
method calculations assume a new luminaire with fresh lamps. For
this reason a suitable light-loss factor must be introduced. This
factor was chosen to be 0.70 for our campus, which does not use
group relamping. A facility using group relamping would have a higher
factor which allows more aggressive retrofits.
We characterize the degree to which each space is over- or under-lit
by a calculated quantity F, called the Fullratio, which is defined
to be the (required illuminance) / (available illuminance).
F = (maintained illuminance recommended by the IES)
= (cavity-ratio calculated illuminance) * (0.70)
Care must be taken in interpreting F, because its value is based
on a calculation of average illuminance throughout a space. Partitions,
luminaire/worktable relative position, and other factors can invalidate
the calculation. For this reason the surveyor's room sketch is used
to detect anomalous conditions.
If F=1, then a space has exactly the recommended maintained illuminance.
If F=0.5 a space has twice the recommended level. The value of F
calculated from the data base by software we developed was the main
indicator used to select an appropriate retrofit for each space.
If there are many identical spaces in a building, then one of them
can be selected for cleaning and relamping, followed by illuminance
measurements (after the lamps have aged for at least 100 hours).
This yields greater accuracy than the calculations, but is too costly
to do in all spaces. Some retrofits, such as full light output high-frequency
ballasts and motion controls, are suitable for spaces that are not
overlit. Other retrofits, such as delamping with optical reflectors,
or partial light-output ballasts, are suitable for overlit spaces.
Figure 2 shows retrofits appropriate
to various fullratio ranges.
RETROFIT HARDWARE AND STRATEGIES
In order to reduce lighting energy use it is necessary to focus
on the two components of energy:
ENERGY = POWER x TIME
The basic cost of energy is the product of power and time. Table
3 shows some of the many strategies and lighting retrofit devices
that decrease power level or duration of use.
TABLE 3. STRATEGIES AND HARDWARE
| To Decrease Power Level |
To Decrease Duration of Use |
| High-frequency ballasts |
Timeclocks |
| Delamping (with or without optical reflectors) |
Motion sensors |
| Reduced light output ballasts * |
Photosensors |
| Dimming ballasts * |
Timed switches |
| Replacement of incandescent |
Computer control (EMS) |
These measures are not uniformly applicable throughout a building.
Those marked with an asterisk (*) should only be used in spaces
that can tolerate a decrease in maintained illuminance.
Note that depending on the aesthetic and illuminance requirements,
there are several retrofits that will replace an existing incandescent
source: replacement with a lower wattage halogen capsule source,
replacement with a compact fluorescent lamp (preferably hard-wired
to eliminate the incandescent socket), or elimination of the incandescent
luminaire and replacement with one using a more efficient source.
SPECIFICATION
Quality
Based on the calculated or measured Fullratio, and on the existing
types of luminaires, it is not difficult to select a room-specific
retrofit that will provide adequate maintained illuminance. But
attention must be given to questions of lighting quality. Most existing
luminaires that pre-date the mid-1980s were not designed to maximize
the VDT user's comfort and productivity. Financial constraints limited
us to replacing prismatic lenses with similar lenses, and then only
if the existing lens was in poor condition. However, a retrofit
parabolic diffuser costs around $25.00 per 2' x 4' fixture for a
1/2" cell sheet that is 1/2" thick, and around $35 for
a 1.5" cell sheet that is 1" thick. The salary of the
VDT user inconvenienced by glare from the conventional prismatic
lens greatly exceeds this cost. A small improvement in comfort and
productivity may well be worth the initial cost of the better diffuser.
When improving lighting quality has higher priority, small cell
parabolic louver diffusers can often be used to replace the existing
flat prismatic lens. This results in a low-brightness luminaire
that interferes less with VDT use. A better solution involves the
use of new indirect fixtures, or of direct fixtures with deep-cell
parabolic diffusers.
Specifying Room-specific Retrofits
The data base software returns to the specifier the list of rooms,
each of which having a Fullratio assigned to it either from calculation
or measurement. By taking into account this measure of adequate
illuminance, along with the type of existing lighting system, the
occupancy patterns of the room's users, and the availability of
daylight, the experienced specifier can choose a suitable combination
of retrofits from Figure 2 and Table
3.
IMPLEMENTATION
The data base assembled for analysis of the spaces in a building
can readily incorporate the specified retrofits, and be used to
generate room lists for contractors. These lists present both the
existing lighting system and the specified retrofit for each space
in a building. These lists also provide the means for contractors
to verify the assumed existing conditions, and to note survey errors
and unanticipated field conditions. Invoices may be readily verified
against the room lists, particularly when contractors have provided
quotes for various unit operations that can be coded into the retrofit
description. The software developed during this project is available
under license from the University of California at Berkeley.
COMMUNICATION
There are a great number of information resources and people with
whom the project manager needs to communicate during the various
stages of the project.
Planning
During the planning stage information can be obtained from vendors,
independent testing laboratories, national laboratories, and other
facility managers. Excellent publications are available on lighting
issues [Eley Associates, 1993]. Contractors can be contacted to
obtain price quotes on the anticipated spectrum of work. Proposed
retrofits should be discussed and/or demonstrated to occupants and
maintenance personnel.
Construction
Building managers and occupants must be alerted to impending construction,
and contractor scheduling provided for limited access areas. Contractors
will need training on the required work methods, record keeping,
and on the rules for disposal of hazardous materials generated by
the project.
Follow-up and Maintenance
The facility electricians need to be familiar with the new technologies
being introduced. Hands-on training sessions should be provided,
along with an as-built list of all locations of retrofit lighting
controls.
The storehouse must be given notice to phase out superceeded equipment,
and to stock the new retrofit devices for maintenance use.
ENVIRONMENTAL CONCERNS
In general energy conservation greatly benefits the environment.
As Amory Lovins has stated, "Reducing energy use is the quickest,
safest, most cost-effective way to reduce the emission of greenhouse
gases that accompanies the generation of electricity from fossil
fuels." Reducing energy use also reduces the dependence of
the U.S.A. on imported fuel. Lighting energy conservation has enormous
potential: in the U.S.A. fluorescent lighting consumes around 200
billion kwh/yr, at an annual cost of $14 billion, or 1/10 of the
nation's electric bill. If high-frequency ballasts were universally
adopted the savings would amount to nearly $3 billion per year.
There are, however, some environmental concerns that accompany
a lighting retrofit. Contract documents should specify that both
ballasts and lamps receive proper disposal. Under the Toxic Substances
Control Act of 1976, old ballasts that are not labeled "No
PCBs" must be handled as toxic waste. Contractors must pack
the ballasts in storage drums at a designated site on the premises,
for shipment by a licensed hauler to ultimate disposal. In addition
the contractors must be trained to properly deal with leaking ballasts
that may contain PCBs. Additional information can be obtained from
the U.S.E.P.A. We currently are paying around $4.00 per ballast
for disposal.
Fluorescent lamps also contain harmful substances. California Administrative
Code, Sections 66699(b) & 66680(d), discusses proper disposed
of the used lamps. Our campus currently is paying $0.40 per four
foot tube for this service, which requires that contractors store
the used lamps in cartons at designated transfer points for pickup
by the licensed lamp recycling firm.
RESULTS
The lighting portion of a building's total electrical use varies
greatly depending on the other energy consuming activities in the
building. Although we typically reduced lighting energy in each
building by 20% - 40%, this amounted to 5% - 36% of the building
total use.
Because lighting in campus buildings is not separately metered,
the reduction caused by our retrofit program was inferred from the
drop in a building's total electrical use following completion of
the lighting retrofit.
Figure 3 is based on one-year moving
averages of a building's monthly total electrical use. The figures
shows how we fit a straight line to the building's consumption for
several years prior to the retrofit. The difference between this
straight line projection and the actual consumption is taken to
represent the energy savings attributable to the lighting retrofit.
OTHER ISSUES
Power Quality
Power quality describes distortions of voltage waveform and changes
in the voltage-current phase relation. Table 4 presents measured
values [Wolsey, 1995] that characterize the performance of some
office equipment.
TABLE 4. POWER QUALITY CHARACTERISTICS
| Device |
AP, watts |
PF |
CTHD, % |
THC, amps |
| 100 W A-lamp |
101 |
1.0 |
1 |
0.008 |
| 13 W CFL with electronic ballast (normal PF) |
13 |
0.50 |
153 |
0.33 |
| 40 W T-12 lamps with efficient magnetic ballast |
87 |
0.98 |
17 |
0.13 |
| 40 W T-12 lamps with electronic ballast |
72 |
0.99 |
5 |
0.03 |
| 32 W T-8 lamps with electronic ballast |
63 |
0.98 |
6 |
0.03 |
| Computer with color monitor |
82 |
0.56 |
138 |
1.68 |
| Laser printer (while printing) |
799 |
0.98 |
15 |
1.02 |
In Table 4, AP=active power, PF=power factor, CTHD=current total
harmonic distortion, and THC=total harmonic current. THC is calculated
from THC = {(CTHD/100)(AP)}/{(PF) (120)}, following [Wolsey, p.6].
The table presents measurements on specific equipment. Specifiers
can obtain similar data from manufacturers or independent compilations
[Ji, 1996].
The table shows that electronic ballasts do not necessarily produce
more harmful harmonic current than do magnetic ballasts or common
office equipment. Even if the measured T-8 system had CTHD=20%,
it would then have THC= 0.10, still less than the T-12 system with
efficient magnetic ballast. An electronic device affects power quality
in a building in proportion to its share of the total building load.
Concerns at a facility about the effects of a lighting retrofit
on power quality and excess neutral wire currents should be evaluated
by a qualified electrical engineer.
Electromagnetic Interference (EMI)
Under certain circumstances electronic devices emit conducted or
radiated electromagnetic waves that can interfere with proper operation
of theft detection systems, infrared controls, cordless telephones,
radios, and power line carrier controls. Descriptions of these potential
problems and possible solutions are discussed in [Buddenberg &
Fowler, 1995]. The only problem we had on campus, after installing
electronic ballasts throughout classroom and laboratory buildings,
was interference with a library theft detection system. This was
easily corrected by replacing ballasts near the detector with magnetic
ballasts.
REFERENCES
Abesamis, R., Black, P., and Kessel, J., Field Experience with
High-Frequency Ballasts, IEEE Transactions On Industry Applications,
Vol. 26, No. 5, September/October 1990.
Buddenberg, A., Fowler, A., Electromagnetic Interference Involving
Fluorescent Lighting Systems, Lighting Answers, Vol. 2, No.
1, March, 1995, Lighting Research Center, Troy, N.Y. 12180-3590
Eley Associates, Advanced Lighting Guidelines: 1993 (Revision
1), Electric Power Research Institute, Publication TR-101022s
Rev.1, May 1993. For information on ordering this and other EPRI
lighting publications, telephone 510-934-4212.
Ji, Y. , Power Quality, Lighting Answers, Vol. 2, No.2,
February, 1995, Lighting Research Center, Troy, N.Y. 12180-3590.
Kessel, J., Performance of Retrofit Optical Reflectors,
Strategic Planning for Energy and the Environment, Vol. 10, No.
2, Fall 1990.
Wolsey, R. , Power Quality, Lighting Answers, Vol. 2, No.2,
February, 1995, Lighting Research Center, Troy, N.Y. 12180-3590.
FIGURES
|