|
Performance of Retrofit Optical Reflectors
Jeffrey Kessel (retired)
University of California
Physical Plant-Campus Services
Energy And Engineering Services
Berkeley, CA 94720
January 10, 1991
Related Reports:
Managing a Large Lighting Retrofit Project
Field Experience with High-Frequency Ballasts
ABSTRACT
The illuminance distributions of two typical fluorescent luminaires,
a 2F40 and a 4F40, were measured before and after removal of one-half
the lamps and stallation of various specular optical reflectors.
The modified fixtures' fluxes were calculated by area-weighting
the measured illuminance distributions, and were found to be 59%-73%
of that of the unmodified fixture. This was accompanied by a 16%-19%
decrease in the distance perpendicular to luminaire axis at which
the illuminance dropped to one-half of its value directly under
the fixture. These results were used to predict the life-cycle costs
of the candidate reflectors when used with commercially available
partial light-output ballasts.
INTRODUCTION
The installation of a specular optical reflector into a fluorescent
luminaire, accompanied by removal of some lamps and ballast, has
gained acceptance as a means to decrease lighting energy use by
nearly one-half, without losing a proportional amount of useful
light.[1] Other investigators [2,3] have found that illuminance
levels decreased to 58% - 65% of original levels after similar modifications.
These results agree with photometric data from one luminaire manufacturer
[4] who offers several luminaires in two versions, differing only
in the reflector material. The CU tables show an increase of 11%
- 26% in the CU values of the specular fixture relative to the new
fixture with standard white diffuse reflector. Other manufacturers
offer new fixtures with specular reflectors [5]. Because specular
reflectors are incorporated into the design from the beginning,
rather than as a retrofit add-on, we may expect to see still higher
efficiencies and greater uniformity of illuminance.
As part of the contracting procedure in the Lighting Modification
Program of the Department of Facilities Management at the University
of California at Berkeley, we carried out a procedure to quantify
this effect. In order to show the range of possibilities for this
type of retrofit, we selected two different luminaire types in the
same building for the performance test. Four reflector manufacturers
produced for testing prototypes encompassing design and material
of their choice, and submitted bids to supply the reflectors. In
order to encourage use of superior design and materials we incorporated
into our request for bids a procedure to give performance-based
credits to the bids of the better performing reflectors.
Our results should be characteristic of the performance obtainable
from retrofit specular reflectors designed under competitive conditions.
Two fixtures, (Type A, a 2'x4' 4F40 with a wrap-around clear prismatic
pattern #12 lens, and Type B, a 1'x4' surface-mounted 2F40 with
a flat clear prismatic pattern #12 lens), were loaned in the summer
of 1987 to four reflector contractors for design of prototype reflectors,
to be submitted with a bid to supply and install 1550 and 1000 units,
respectively. The request for bid specified the manner in which
a credit, proportional to performance, would be applied to the bids.
The reflectors produced were of different design and materials,
and are representative of typical commercially available products.
The fixture and reflector characteristics are listed in Table 1.
Table 1. Optical Reflector Performance Measured at the University
of California, Berkeley, Summer,1987
| |
Candidate: |
Ref-1A |
Ref-2A |
Ref-3A |
Ref-4A |
| |
Material: |
Anod. Alum. |
Anod. Alum. + DEO |
Anod. Alum. |
Silver Laminate |
| |
Coverage: |
Full |
Full |
Full |
Full |
| A: (2' x 4') |
Sockets: |
Relocate |
Relocate |
No relocate |
No relocate |
| |
% Base FC: |
64 |
71 |
59 |
71 |
| |
Bid: |
$40.00 |
41.00 |
$39.00 |
$63.00 |
| |
Adjusted Bid: |
$30.00 |
$18,00 |
$39.00 |
$40.00 |
| |
|
|
|
|
|
| |
Candidate: |
Ref-1B |
Ref-2B |
Ref-3B |
Ref-4B |
| |
Material: |
Anod. Alum. |
Anod. Alum. + DEO |
Anod. Alum. |
Silver Laminate |
| |
Coverage: |
Full |
Full |
Partial |
Full |
| B: (1' x 4') |
Sockets: |
Relocate |
Relocate |
No relocate |
No relocate |
| |
R=% BaseFC: |
65 |
71 |
61 |
73 |
| |
Bid: |
$40.00 |
$28.00 |
$38.00 |
$46.00 |
| |
Adjusted Bid: |
$34.00 |
$15.00 |
$38.00 |
$31.00 |
Notes to Table 1:
-
Type A is a 2' x 4' pendant-mounted 4F40 with wraparound prismatic
lens.
-
Type B is a 1' x 4' 2F40 surface-mounted fixture with flat
prismatic lens.
-
Partial or Full Coverage refers to the size of the reflector
relative to the size of the fixture. Relocate indicates that
the original socket holders were removed and replaced with relocated
sockets.
-
Anod. Alum. is high quality anodized aluminum. DEO indicates
the addition of a dielectric overcoat to increase reflectance.
Silv. Laminate refers to a coating of elemental silver deposited
on plastic sheet which is adhered to aluminum substrate.
-
The Bid prices quoted were to clean the fixture and to supply
and install the reflector (and socket mounting brackets, if
any), to supply and install lamps, and to install a ballast
supplied by the University. The Adjusted Bid is the performance-adjusted
bid price as explained below in the section on Reflector Selection.
R=% Base Flux = % of flux from original fixture (after being
cleaned and relamped).
PROCEDURE
The test procedure was similar for categoriesA and B. Both test
luminaires were over twenty years old, and had rarely been cleaned.
A classroom measuring 26.5 ft. x 37.0 ft. x 14.7 ft. high, with
fixtures suspended at 9.0 ft. height, was selected for the CategoryA
test. An office measuring 17.0 ft. x 21.0 ft. x 9.8 ft. high, with
fixtures suspended at 9.5 ft. height, was selected for the Category
B test.
First a fixture located near the center of the test room was thoroughly
cleaned, and fitted with a full complement of 40 w. F40/CW lamps
which had been operated under controlled conditions in a lamp-life
test rack for 4000 hours. The fixture's 277 v. ballast was removed
and replaced with energy-efficient 120 v. core & coil ballast
(Advance R-2S40-1-TP for category A, and Universal 412-L-SLH-TC-P
for category B) operating initially the full lamp complement, and
subsequently one half the lamps in the modified fixture. The test
ballast was powered by a line voltage regulated power supply to
ensure that illuminance measurements of modified fixtures would
be obtained at the same power level.
Power consumption was monitored with a TIF 2000 Wattprobe, and
found to remain within a 2% range during illuminance measurements
on the test grid by means of a Tektronix J65 illuminance probe.
All luminaires in the room were switched off except for the test
fixture. Air temperature near the test fixture was monitored with
a Fluke Y8103 Type K thermocouple, and building fans were switched
off in a successful effort to maintain the room at constant temperature
(20.5 C).
A test grid of twelve points, 2.5 ft. above the floor, was laid
out in one 8.75 ft. x 8.75 ft. quadrant of the luminaire. Figure
1 shows the grid for the two tests. Each reflector contractor
in turn installed his reflector, most choosing to relocate lamp
sockets as part of their design. The test lamps and the sockets
were marked to ensure that each reflector was tested with the same
lamps installed with the same orientation (end-for-end and rotationally
about lamp axis). There was, of course, some lateral displacement
of the lamps depending upon the contractor's design location for
the lamp sockets. After waiting 10 minutes until the power consumption
stabilized, illuminance measurements were taken on the grid.
RESULTS
The measured power decreased, for the category A luminaire, from
163 w. (unmodified, 4 lamps) to 91 w. (modified, 2 lamps). The modified
category B luminaire operated at 47 w. (with one lamp). The unmodified
category B luminaire's power was not measured because it was powered
by its original 277 v. 2F40 ballast during the baseline (unmodified)
illuminance measurements.
In Table 1 the photometric results are summarized by stating R,
the percent of unmodified (base) luminaire flux delivered by the
modified luminaire. This ranged from 59%-71% for Category A, and
from 61%-73% for Category B. Figure 2 and
Figure 3 plot the illuminance along a line
perpendicular to the luminaires' major axis. The decreased lateral
light distribution attributable to the reflectors is indicated by
a 16%-19% decrease in the distance at which the illuminance drops
to one-half its maximum value (as indicated by the arrows labelled
1/2 Max).
REFLECTOR SELECTION
Rather than award the contract to the low bidder, the request for
bids specified award to the low bidder after a downward adjustment
that was proportional to the relative performance of the reflectors.
This adjustment factor is derived as follows:
Let R be the ratio of flux delivered to four quadrants by the modified
luminaire relative to the unmodified luminaire: (delamped &
reflectorized)/(fully-lamped basecase).
Consider two reflectorized fixtures, 1 and 2, with ratios R1 <
R2, (R calculated relative to the fully-lamped basecase). By using
commercially available [6] "tuned" partial light output
ballasts we can operate the poorer performing reflector at full
power Power1 = W, and the better performing fixture 2 at partial
power Power2, so that its resultant ratio R2 equals that of fixture
1 operated at full power. That is, decrease Power2 until Power1
/ Power2 = W/Power2 = R2/R1.
Because the ballast used with fixture 1 consumes W watts, we have:
Therefore the lifecycle avoided energy cost of retrofit fixture
2 relative to retrofit fixture 1 is, per fixture:
where W=ballast power, H=annual operating hours, E= current cost
of electricity, and [P/A] is the present worth factor encompassing
anticipated lifetime, discount rate, and energy cost escalation
rate.
In our contract award, this avoided energy cost factor was used
to adjust downward the bids of the better performing reflectors.
Thus all retrofit fixtures were evaluated as if they operated with
partial power so as to have the same illuminance ratio as the worst
performing reflector (which itself in effect receives an adjustment
of $0.00). The rationale for this adjustment is that we select as
candidate spaces for reflector retrofit those spaces calculated
(or measured) to have a factor of excess illuminance which we anticipate
will be "corrected" by delamping and installation of a
poorer performingreflector. The extra illuminance provided by a
better performing reflector may be captured as energy savings through
the use of partial light output ballast, or may be allowed to remain
as an amenity with the use of full power ballast. These adjustments
ranged from $10.55-22.82 for category A (W=60, H=3000, E=0.075,
and [P/A]=10), and from $5.54-$14.79 for category B (W=30, H=4000,
E=0.075, and P/A=10). The adjusted bids are shown as the last entry
for each reflector in Table 1.
CONCLUSIONS
The removal of one-half the lamps combined with the installation
of specular optical reflectors as a retrofit modification for fluorescent
luminaires resulted in useful delivered flux in the range of 60%
- 73% of that obtained with a cleaned older fully-lamped luminaire.
This performance range is a function of reflector design and material.
Lighting energy use can be approximately halved in spaces that can
tolerate both a decrease in illuminance of this magnitude, and a
decrease in uniformity characterized by a decrease of around 16%
in the half-peak spacing. This range in reflector performance can
be quantified and used as input to a life-cycle cost analysis which
in turn can be used to adjust the bid prices for award of a contract.
ACKNOWLEDGEMENTS
The author wishes to thank Robert Clear and Rudy Verderber of the
Lighting Systems Research Group at Lawrence Berkeley Laboratory
for their encouragement and helpful suggestions and comments.
REFERENCES AND FOOTNOTES
1) Chester K. Johnston, Lighting Energy Management - With Reflectors,
Facilities Manager, Vol. 1, No. 4, Winter 1985
2) D. L. DiLaura and D.G. Kambich, Luminaire Retrofit Performance
- Commercial Building Lighting Systems, March, 1987,
EPRI Report EM-5094, Palo Alto, CA 94304
3) T.K. McGowan, Fluorescent Fixture Reflector Inserts,
General Electric Technical Information Series, No.4162-871A, January
22, 1987.
4) Fixtures 101, 103, 325 are offered with and without a silver-laminate
specular reflector. Wellmade Metal Products, Oakland, CA.
5) Brayer Lighting, San Francisco, CA ; Maximum Technology, Brisbane,
CA ; Wellmade Metal Products, Oakland, CA
6) Electronic Ballast Technology, Inc., Torrance, CA
FIGURES
|